Solivia Series 10-11 kVA

The TR series provide extended functionality for all grids.
An automatic power balancing for the three phases is integrated and ensures that the inverters always balance the feed-in over all phases.

The combination of transformer-based technology and protection degree IP65 allows the inverters to be used in harsh enviroments. When PV modules are used that need to be grounded, these inverters are the ideal choice. They support negative and positive grounding and offers several monitoring methods.

The inverters allow input voltages from 375 V to 1000 V (full power range from 380 V to 850 V). Operating temperatures range up to 70 °C (derating does not start before 55 °C)

Max. recommended PV power:
Nominal power:
Voltage range:
Full power MPP range:
Nominal current:
Max. current:

12.1 kWp
10.6 kW
375 … 1000 V
380 … 850 V
17.7 A @ 600 V
26.4 A

Nominal apparent power:
Voltage range:
Nominal current:
Nominal frequency:
Frequency range:
Power factor adjustable:
Total harmonic distortion (THD):

10 kW
3 x 400 V + N + PE (+18/-20%)
14.5 A
50 Hz
50 ± 5 Hz
0.8 cap … 0.8 ind
< 5 % @ nominal power

Max. efficiency:
Operating temperature:
Full power without derating:
Storage temperature:
Humidity:
Max. operating altitude:

96.8 %
-25 … +70 °C
-25 … +58 °C
-25 … +80 °C
0 … 95 %
2000 m (above sea level)

Size (H x W x D):
Weight:
Cooling:
AC connector:
DC connector:
Communication interfaces:
DC disconnector:
Display:

685 x 410 x 185 mm
39 kg
Convection with fan (plug & play)
Amphenol C16/3
3 pairs of Multi-Contact MC4
2 x RS485 (RJ45) + 1 USB A 2.0
Integrated
3 LEDs, 4-line LCD

Protection degree:
Safety class:
Configurable trip parameters:
Insulation monitoring:
Overload behavior:
EMC:

Safety:
Anti-islanding protection / Grid regulation:

IP65 / IP54
I
Yes
Yes
Current limitation; power limitation
EN 61000-6-2; EN 61000-6-3; EN 61000-3-11; EN 61000-3-12
IEC 62103; IEC 62109-1 / -2
VDE 0126-1-1; France/Islands (60 Hz); UTE C15-712-1; RD 661/2007; RD 1699/2011; RD 1663/2000; Synergrid C10/11 (06/2012); EN 50438; G59/1-2; VDE-AR-N 4105; VFR 2013; VFR 2014

Max. recommended PV power:
Nominal power:
Voltage range:
Full power MPP range:
Nominal current:
Max. current:

13.3 kWp
11.6 kW
375 … 1000 V
380 … 850 V
19.5 A @ 600 V
29.0 A

Nominal apparent power:
Voltage range:
Nominal current:
Nominal frequency:
Frequency range:
Power factor adjustable:
Total harmonic distortion (THD):

11 kVA
3 x 400 V + N + PE (+18/-20%)
16.0 A
50 Hz
50 ± 5 Hz
0.8 cap … 0.8 ind
< 5 % @ nominal power

Max. efficiency:
Operating temperature:
Full power without derating:
Storage temperature:
Humidity:
Max. operating altitude:

96.8 %
-25 … +70 °C
-25 … +55 °C
-25 … +80 °C
0 … 95 %
2000 m (above sea level)

Size (H x W x D):
Weight:
Cooling:
AC connector:
DC connector:
Communication interfaces:
DC disconnector:
Display:

685 x 410 x 185 mm
39 kg
Convection with fan (plug & play)
Amphenol C16/3
3 pairs of Multi-Contact MC4
2 x RS485 (RJ45) + 1 USB A 2.0
Integrated
3 LEDs, 4-line LCD

Protection degree:
Safety class:
Configurable trip parameters:
Insulation monitoring:
Overload behavior:
EMC:

Safety:
Anti-islanding protection / Grid regulation:

IP65 / IP54
I
Yes
Yes
Current limitation; power limitation
EN 61000-6-2; EN 61000-6-3; EN 61000-3-11; EN 61000-3-12
IEC 62103; IEC 62109-1 / -2
VDE 0126-1-1/A1; France/Islands (60 Hz); UTE C15-712-1; RD 661/2007; RD 1699/2011;RD 1663/2000; Synergrid C10/11 (06/2012); EN 50438; G59/1-2; VDE-AR-N 4105; VFR 2013; VFR 2014; BDEW