The inverters use an innovative heatsink design for cooling which draws the heat away from the inverter through a natural convection process. Because there are no fans required, maintenance costs are reduced and audible noise is greatly reduced. Additionally, the intelligent cooling design extends the life of electronic components and increases the life of the solar Inverter.

Max. recommended PV power:
Nominal power:
Voltage range:
Full power MPP range:
Max. current:
Max. number of MPP trackers:

Input load:

7500 Wp
6500 W
200 … 1000 V
318 … 800 V
20 A (10 A per MPP tracker)
Parallel inputs: 1 MPP Tracker, Separate inputs: 2 MPP Trackers
Symmetrical

Nominal apparent power:
Voltage range:
Nominal frequency:
Power factor adjustable:
Total harmonic distortion (THD):

6000 VA
3×230 / 400V (± 20 %) (3/PE or 3/N/PE)
50/60 Hz +- 5%
0.8 cap … 0.8 ind
<3 % @ nominal apparent power

Max. efficiency:
Operating temperature:
Full power without derating:
Storage temperature:
Humidity:
Max. operating altitude:

98.3 %
-25 … +60 degrees C
-25 … +40 degrees C
-25 .. +60 degrees C
0 … 95 %
2000m (above sea level)

Size (H x W x D):
Weight:
Cooling:
AC connector:
DC connector:
Communication interfaces:
DC disconnector:
Display:

510 x 445 x 117 mm
24.5 kg
Convection cooling
Amphenol C16-3
2 pairs of Multi-Contact MC4
2 x RJ45 / RS485
Integrated
2 LEDs, 4-line LCD

Protection degree:
Safety class:
Configurable trip parameters:
Insulation monitoring:
Overload behavior:
Anti-islanding protection / Grid regulation:
Safety:
EMC:

IP65
I
Yes
Yes
Current limitation; power limitation
VDE 0126-1-1; VDE-AR-N 4105
IEC62109-1 / -2; CE compliance
EN61000-6-2; EN61000-6-3; EN61000-3-2; EN61000-3-3

Max. recommended PV power:
Nominal power:
Voltage range:
Full power MPP range:
Max. current:
Max. number of MPP trackers:

Input load:

10000 Wp
8600 W
200 … 1000 V
415 … 800 V
20 A (10 A per MPP tracker)
Parallel inputs: 1 MPP Tracker, Separate inputs: 2 MPP Trackers
Symmetrical

Nominal apparent power:
Voltage range:
Nominal frequency:
Power factor adjustable:
Total harmonic distortion (THD):

8000 VA
3×230 / 400V (± 20 %) (3/PE or 3/N/PE)
50/60 Hz +- 5%
0.8 cap … 0.8 ind
<3 % @ nominal apparent power

Max. efficiency:
Operating temperature:
Full power without derating:
Storage temperature:
Humidity:
Max. operating altitude:

98.3 %
-25 … +60 degrees C
-25 … +40 degrees C
-25 .. +60 degrees C
0 … 95 %
2000m (above sea level)

Size (H x W x D):
Weight:
Cooling:
AC connector:
DC connector:
Communication interfaces:
DC disconnector:
Display:

510 x 445 x 117 mm
24.5 kg
Convection cooling
Amphenol C16-3
2 pairs of Multi-Contact MC4
2 x RJ45 / RS485
Integrated
2 LEDs, 4-line LCD

Protection degree:
Safety class:
Configurable trip parameters:
Insulation monitoring:
Overload behavior:
Anti-islanding protection / Grid regulation:
Safety:
EMC:

IP65
I
Yes
Yes
Current limitation; power limitation
VDE 0126-1-1; VDE-AR-N 4105
IEC62109-1 / -2; CE compliance
EN61000-6-2; EN61000-6-3; EN61000-3-2; EN61000-3-3

Max. recommended PV power:
Nominal power:
Voltage range:
Full power MPP range:
Max. current:

Max. number of MPP trackers:

Input load:

12500 Wp
10800 W
200 … 1000 V
415 … 800 V
25 A (15A/10A per MPP tracker)
Parallel inputs: 1 MPP Tracker, Separate inputs: 2 MPP Trackers
Symmetrical / Asymmetrical (33 / 67 %)

Nominal apparent power:
Voltage range:
Nominal frequency:
Power factor adjustable:
Total harmonic distortion (THD):

10000 VA
3×230 / 400V (± 20 %) (3/PE or 3/N/PE)
50/60 Hz +- 5%
0.8 cap … 0.8 ind
<3 % @ nominal apparent power

Max. efficiency:
Operating temperature:
Full power without derating:
Storage temperature:
Humidity:
Max. operating altitude:

98.3 %
-25 … +60 degrees C
-25 … +40 degrees C
-25 .. +60 degrees C
0 … 95 %
2000m (above sea level)

Size (H x W x D):
Weight:
Cooling:
AC connector:
DC connector:
Communication interfaces:
DC disconnector:
Display:

510 x 445 x 117 mm
26 kg
Convection cooling
Amphenol C16-3
3 pairs of Multi-Contact MC4
2 x RJ45 / RS485
Integrated
2 LEDs, 4-line LCD

Protection degree:
Safety class:
Configurable trip parameters:
Insulation monitoring:
Overload behavior:
Anti-islanding protection / Grid regulation:
Safety:
EMC:

IP65
I
Yes
Yes
Current limitation; power limitation
VDE 0126-1-1; VDE-AR-N 4105
IEC62109-1 / -2; CE compliance
EN61000-6-2; EN61000-6-3; EN61000-3-11; EN61000-3-12